Speed (m/min) | Overhead (OH) | Pit (PP) | M/C Room Height (MH) |
30, 45 | 4400 | 1200 | 2200 |
60 | 4600 | 1500 | 2200 |
90 | 4800 | 1800 | 2400 |
105 | 5000 | 2100 | 2400 |
Type | Model | Speed | Clear Opening - OP | Car Internal - CA x CB | Car External - A x B | Hoistway X x Y | M/C Room - MX x MY | M/C Room Reaction (kg) - R1 | M/C Room Reaction (kg) - R2 |
Standard | B750-2S | 30,45, 60 | 1100 | 1300X 2300 | 1360X 2490 | 2050X 2850 | 2300 X3500 | 5790, 5900 | 3450,3750 |
Standard | B1000-2S | 30,45, 60 | 1200 | 1500X 2500 | 1560X 2692 | 2300X 3050 | 2750 X4000 | 6500,6800 | 3700,4100 |
Double | B750-2SD | 30,45 ,60 | 1100 | 1300X 2300 | 1360X 2634 | 2050X 3000 | 2300 X3500 | 5790,5900 | 3450,3700 |
Double | B1000-2SD | 30, 45,60 | 1200 | 1500X 2500 | 1560X 2834 | 2450X 3200 | 2750 X4000 | 9300,9500 | 3700,4100 |
1. The temperature of the machine room must be kept below 40℃ with a ventilation fan or air conditioner.
If possible, the humidity should be less than 90%.
2. If the hoistway is unusual or the height of the machine room is high, it may be larger than the figure below.
3. The figures below are minimum values.
1. Please contact DSIDS for non-standard capacity or dimensions.
2. The above dimensions apply only to the basic door.
When a fire door is applied, the hoistway size of 1 car must be added by 100mm from the X dimension.